The Use and Principle of Current Transformer Acrel Support Olympic Winter Games Beijing 2022 Power Supply Solution for Winter Olympics Wireless Temperature Solution at Beijing Daxing International Airport Acrel Releases ADW300 with 333mV Access Energy meters used in urban comprehensive pipe gallery projects Working Principles and Wiring of Various Types of Electric Meters Digital Electric Energy Meter VS Electronic Electric Energy Meter Problems and Common Fault Analysis of Current Transformers During Operation Detection and Marking of Current Transformers The Functions and Working Principles of Current Transformers Application of DC Current Meters in Substation DC Measurement Operation Methods and Precautions of Current Transformers The Detection and the Open Circuit Fault Inspection of Current Transformers Models, Structures and Installation Methods of Different Hall Current Sensors The Working Principles of the DC Current Shunts How to Set the Temp and Humidity Controller? Precautions of Multifunction Meter Storage Principle and Characteristic Parameters of Hall Current Sensor Multi-function Instrument Definition and Troubleshooting The Use of Prepayment Energy Meter and Its Advantages over Induction Meter Basic Functions of Smart Prepaid Electricity Meter in Student Dormitories How to Use the Multi Function Energy Meter? What Functions Does It Have? Factors That Affect the Performance and Use Value of Prepayment Energy Meter Application of ​IoT Based Electricity Energy Meter Application of Wireless Temperature Sensor in Press What is the Significance of Smart Energy Meter Applications? Smart Energy Meter Application What Are the Common Faults of Current Transformers? Operation Precautions of Current Transformers and the Cause of Burning The Principle and Use of Through-core Current Transformers The Wiring Principle of Current Transformers Design Features of Wireless Temperature Sensors Errors of Daily Current Transformers

ACR10R-D16TE



acr10r d16te


Wiring

Technical Parameters

Dimension

It is recommended to use 0.5A or 3A for the fuse in the connection diagram;

RS485 communication terminal connection can use either RJ45 female or normal connector

wiring.png

Model


ACR10R-D16TE

Input

Phase

Single phase

Frequency

45~65Hz

Voltage

Rated voltage:AC 100V 400V

Overload:1.2 times the rated voltag(continuous);2 times the rated voltage lasting for 1 second

Power consumption:less then 0.2VA

Current

Max current:120A

Overload:1.2 times the rated current(continuous);10 times the rated current lasting for 1second

Power consumption:less then 0.2VA

Output

Communication

RS485 interface,Modbus—RTU

Display

LCD

Measurement precision

Voltage:0.2 level,current,power Active energy:0.5 level,0.01Hz frequency,Reactive energy:1 level

Split CT size

Through size 16mm

Power supply

AC 85~265V or DC 100~350V;power consumption≤10VA

Safety

Power frequency withstand voltage

AC2kV 1min between power supply,current input ,voltage input and communication

AC2kV 1 min between each pair of combinations among power supply,current input and voltage input

Insulation resistor

Input,output terminal to housing>100MΩ

Environment

Working temperature

-10℃~55℃

Storage temperature

-20℃~70℃

Relative humidity

5%~95%,non-condensing

Altitude

≤2500m

acr-10r-technical.png

dimension2.png