The Use and Principle of Current Transformer Acrel Support Olympic Winter Games Beijing 2022 Power Supply Solution for Winter Olympics Wireless Temperature Solution at Beijing Daxing International Airport Acrel Releases ADW300 with 333mV Access Energy meters used in urban comprehensive pipe gallery projects Working Principles and Wiring of Various Types of Electric Meters Digital Electric Energy Meter VS Electronic Electric Energy Meter Problems and Common Fault Analysis of Current Transformers During Operation Detection and Marking of Current Transformers The Functions and Working Principles of Current Transformers Application of DC Current Meters in Substation DC Measurement Operation Methods and Precautions of Current Transformers The Detection and the Open Circuit Fault Inspection of Current Transformers Models, Structures and Installation Methods of Different Hall Current Sensors The Working Principles of the DC Current Shunts How to Set the Temp and Humidity Controller? Precautions of Multifunction Meter Storage Principle and Characteristic Parameters of Hall Current Sensor Multi-function Instrument Definition and Troubleshooting The Use of Prepayment Energy Meter and Its Advantages over Induction Meter Basic Functions of Smart Prepaid Electricity Meter in Student Dormitories How to Use the Multi Function Energy Meter? What Functions Does It Have? Factors That Affect the Performance and Use Value of Prepayment Energy Meter Application of ​IoT Based Electricity Energy Meter Application of Wireless Temperature Sensor in Press What is the Significance of Smart Energy Meter Applications? Smart Energy Meter Application What Are the Common Faults of Current Transformers? Operation Precautions of Current Transformers and the Cause of Burning The Principle and Use of Through-core Current Transformers The Wiring Principle of Current Transformers Design Features of Wireless Temperature Sensors Errors of Daily Current Transformers

The Wiring Principle of Current Transformers


1. Open circuit is not allowed on the secondary side of the CT current transformer


The secondary open circuit may have serious consequences, one is that the iron core is overheated, and even the transformer is burned; the other is that due to the large number of turns of the secondary winding, a risky high voltage will be induced, endangering the safety of people and equipment.


Since the secondary winding of the current transformer cannot be opened, the windings that are not used by the current transformer need to be short-circuited. However, for a current transformer with multiple taps, the unused taps should be empty and cannot be short-circuited. For example, a current transformer has secondary taps 1S1, 1S2, and 1S3, of which 1S1 and 1S2 are 300/5A, and 1S1 and 1S3 are 600. /5A, when 300/5A is required, connect 1S1 and 1S2 for use, and should not short-circuit 1S1 and 1S3, otherwise it will affect the improved accuracy of the tap.


2. The secondary side of the high-voltage CT current transformer must be grounded at one point


Since the primary side of the high-voltage current transformer is high-voltage, when the high-voltage breakdown occurs between the primary and secondary coils due to insulation damage, the high-voltage will enter the low-voltage. Safety of persons and equipment. However, it should be noted that the secondary circuit of the current transformer is only allowed to be grounded at one point, and no more grounding is allowed, otherwise it may cause shunt and affect the use.


The secondary coil of the low voltage current transformer should not be grounded. Due to the low voltage of the low-voltage transformer, the insulation strength between the primary and secondary coils is high, and the possibility of breakdown of the primary and secondary coils is small. In addition, the ungrounded secondary coil will make the secondary circuit and the instrument insulation. The performance is improved, and the accident of the instrument being burned by the lightning strike can also be reduced.


In addition, differential maintenance is composed of differential relays (such as BCH-2, etc.), and the current transformers on both sides of differential maintenance can only be grounded at one point. Generally, the grounding point is set at the maintenance screen, and when differential maintenance uses During the maintenance and installation of the computer, the current transformers on both sides should be grounded separately.


3. The improvement level and maintenance level of the CT current transformer cannot be wrongly connected


Due to the different thicknesses of the winding iron core design for improvement and maintenance, if the connection is wrong, firstly, the improved accuracy during normal operation will be reduced, and the electric energy measurement will be inaccurate; When the short-circuit current exceeds a certain multiple of the rated current, the iron core is saturated, limiting the growth of the secondary current to maintain the meter. The core of the relay maintenance winding is not saturated, and the secondary current increases accordingly with the short-circuit current, so that the action of the relay maintenance is performed. If the connection is wrong, the relay maintenance action will be inflexible, and the meter may burn out.


When connecting the metering winding of the current transformer and the relay maintenance winding that is involved in the direction, control two points to confirm the connection. One is to look at the installation position of the current transformer, that is, to determine which side of the L1 installation of the current transformer is; the second is to look at the winding. Function or relay maintenance type, the secondary wiring of the current transformer can be determined by the above two points.