The Use and Principle of Current Transformer Acrel Support Olympic Winter Games Beijing 2022 Power Supply Solution for Winter Olympics Wireless Temperature Solution at Beijing Daxing International Airport Acrel Releases ADW300 with 333mV Access Energy meters used in urban comprehensive pipe gallery projects Working Principles and Wiring of Various Types of Electric Meters Digital Electric Energy Meter VS Electronic Electric Energy Meter Problems and Common Fault Analysis of Current Transformers During Operation Detection and Marking of Current Transformers The Functions and Working Principles of Current Transformers Application of DC Current Meters in Substation DC Measurement Operation Methods and Precautions of Current Transformers The Detection and the Open Circuit Fault Inspection of Current Transformers Models, Structures and Installation Methods of Different Hall Current Sensors The Working Principles of the DC Current Shunts How to Set the Temp and Humidity Controller? Precautions of Multifunction Meter Storage Principle and Characteristic Parameters of Hall Current Sensor Multi-function Instrument Definition and Troubleshooting The Use of Prepayment Energy Meter and Its Advantages over Induction Meter Basic Functions of Smart Prepaid Electricity Meter in Student Dormitories How to Use the Multi Function Energy Meter? What Functions Does It Have? Factors That Affect the Performance and Use Value of Prepayment Energy Meter Application of ​IoT Based Electricity Energy Meter Application of Wireless Temperature Sensor in Press What is the Significance of Smart Energy Meter Applications? Smart Energy Meter Application What Are the Common Faults of Current Transformers? Operation Precautions of Current Transformers and the Cause of Burning The Principle and Use of Through-core Current Transformers The Wiring Principle of Current Transformers Design Features of Wireless Temperature Sensors Errors of Daily Current Transformers

What Are the Common Faults of Current Transformers?


Common failures of current transformers are often related to manufacturing shortcomings, as detailed below:


1. The insulation of the CT current transformer is very thick, some insulation wraps are loose, and there are wrinkles between the insulation layers. In addition, the vacuum treatment is poor, and the impregnation is incomplete to form an air-containing cavity, which is easy to cause partial discharge failure.


2. The size and arrangement of the capacitive screen of the CT current transformer do not meet the design requirements, so as to discharge the capacitive screen at least, the capacitive plate is not lubricated and flat, and even dislocated or broken, which destroys the voltage equalization characteristics. Therefore, when the electric field strength along the surface of some solid insulation reaches a certain value, a partial discharge will be formed.


The direct result of the above-mentioned partial discharge is to crack the insulating oil, generate a large amount of x-wax between the insulating layers, and increase the dielectric loss. This discharge has a cumulative effect, and if it continues, the gas-in-oil analysis will likely exhibit the characteristics of arcing.


3. Because the insulating material of the CT current transformer is not clean or contains high humidity, creeping discharge may occur on its surface. This situation is more common when the terminal leads are discharged along the surface of the pad.


4. The loose connection of some current transformers or the potential suspension of metal parts will lead to spark discharge. For example, the primary winding support nut is loose, forming the potential suspension of the primary winding shielding aluminum foil, and the contact of the terminal lead or poor welding leads to disconnection. Fault.


5. The looseness of the splint, bolts and nuts of the primary connection of the CT current transformer, the looseness of the grounding nut of the last screen, the looseness of the tap tightening nut, etc., may increase the contact resistance and cause some overheating failures.


In addition, improper on-site maintenance management should also be paid attention to. For example, if the CT current transformer is wetted by water, it may be related to the sealing structure and sealing material of the manufacturer, but there are also maintenance management problems.


Generally speaking, the on-site vacuum degassing is insufficient or the vacuum drying is not carried out during maintenance, resulting in easy saturation of the dissolved gas in the oil or residual air bubbles and high moisture content in the oil-paper insulation. All of these will leave a security risk to the device.


Founded in 2003, Acrel Co.,Ltd. is a high-tech enterprise integrating R&D, production, sales and service. It mainly provides users with system solutions for energy efficiency management and electricity safety. The "Acrel" smart energy meter manufacturer is equipped with a complete line from cloud platform software to sensors. Welcome to consult.